Part Number Hot Search : 
AT25256 NN514256 CZMA6V8 MBR1060 2SC3970A GT8G121 75N3L 496C156M
Product Description
Full Text Search
 

To Download MTU20V4000DS3200 Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
  diesel generator set mtu 20v4000 ds3200 380v C 11 kv/50 hz/data center continuous power/nea (orde) optimized mtu 20v4000g63l/water charge air cooling product highlights optional equipment and ? nishing shown. standard may vary. // bene? ts - low fuel consumtion - optimized system integration ability - high reliability - high availability of power - long maintenance intervals // mtu onsite energy is a single-source supplier // support - global product support offered // standards - engine-generator set is designed and manufactured in facilities certi? ed to standards iso 2008:9001 and iso 2004:14001 - generator set complies to iso 8528 - generator meets nema mg1, bs5000, iso, din en and iec standards - nfpa 110 // power rating - system ratings: 2650 kva - 2750 kva - accepts rated load in one step per nfpa 110 - generator set complies to g3 according to iso 8528-5 - generator set exceeds load steps according to iso 8528-5 // performance assurance certi? cation (pac) - engine-generator set tested to iso 8528-5 for transient response - 100% load factor - veri? ed product design, quality and performance integrity - all engine systems are prototype and factory tested // complete range of accessories available - control panel - circuit breaker/power distribution - fuel system - fuel connections with shut-off valve mounted to base frame - starting/charging system - exhaust system - mechanical and electrical driven radiators - medium voltage alternators // emissions - nea (orde) optimized // certi? cations - ce certi? cation option
2 // / / mtu 20v4000 ds3200 / 50 hz / 380v - 11kv application data ? // engine manufacturer mtu model 20v4000g63l type 4-cycle arrangement 20v displacement: l 95.4 bore: mm 170 stroke: mm 210 compression ratio 16.4 rated speed: rpm 1500 engine governor adec max power: kwm 2590 air cleaner dry // fuel system maximum fuel lift: m 5 total fuel ? ow: l/min 27 // fuel consumption ? l/hr g/kwh at 100% of power rating: 617.9 198 at 75% of power rating: 479.8 205 at 50% of power rating: 333.9 214 // liquid capacity (lubrication) total oil system capacity: l 390 engine jacket water capacity: l 205 intercooler coolant capacity: l 50 // combustion air requirements combustion air volume: m 3 /s 2.9 max. air intake restriction: mbar 50 // cooling/radiator system coolant ? ow rate (ht circuit): m 3 /h 80 coolant ? ow rate (lt circuit): m 3 /h 32.5 heat rejection to coolant: kw 1020 heat radiated to charge air cooling: kw 480 heat radiated to ambient: kw 105 fan power for mech. radiator (40c): kwm 70 // exhaust system exhaust gas temp. (after turbocharger): c 560 exhaust gas volume: m 3 /s 8.5 maximum allowable back pressure: mbar 85 minimum allowable back pressure: mbar 30 ? all data refers only to the engine and is based on iso standard conditions (25c and 100m above sea level). ? values referenced are in accordance with iso 3046-1. conversion calculated with fuel density of 0.83 g/ml. all fuel consumption values refer to rated engine power.
3 // / / mtu 20v4000 ds3200 / 50 hz / 380v - 11kv // engine 4-cycle standard single stage air ? lter oil drain extension & shut-off valve closed crankcase ventilation with improved oil seperator governor-electronic isochronous common rail fuel injection nea (orde) optimized engine centrifugal oil ? lter // generator nema mg1, bs5000, iso, din en and iec standards self-ventilated superior voltage waveform solid state, volts-per-hertz regulator no load to full load regulation 0,25% voltage regulation no load to full load brushless alternator with brushless pilot exciter 4 pole, rotating ? eld sustained short circuit current of up to 250% of the rated current for up to 10 seconds (marathon generator) ? sustained short circuit current of up to 300% of the rated current for up to 10 seconds (leroy somer generator) marathon low voltage generator ? leroy somer generator ? oversized generator ? medium voltage generator represents standard features ? represents optional features standard and optional features // system ratings (kw/kva) generator model voltage nea (orde) optimized 40c/100m without radiator with mechanical radiator with electr. driven radiator kwel kva* amps kwel kva* amps kwel kva* amps marathon 1030fdl7094 380 v 2200 2750 4178 2120 2650 4026 2160 2700 4102 (low voltage 400 v 2200 2750 3969 2120 2650 3825 2120 2650 3825 marathon standard) 415 v 2200 2750 3826 2120 2650 3687 2120 2650 3687 n.a. 380 v n.a. n.a. n.a. n. a. n.a. n.a. n.a. n.a. n.a. (low voltage 400 v n.a. n.a. n. a. n.a. n.a. n.a. n.a. n.a. n.a. marathon oversized) 415 v n.a. n.a. n. a. n.a. n.a. n.a. n.a. n.a. n.a. leroy somer lsa 54 m75 380 v 2200 2750 4178 2120 2650 4026 2120 2650 4026 (low voltage 400 v 2200 2750 3969 2120 2650 3825 2120 2650 3825 leroy somer) 415 v 2200 2750 3826 2120 2650 3687 2120 2650 3687 marathon 1040fdh7102 11 kv 2200 2750 144 2120 2650 139 2120 2650 139 (medium volt. marathon) leroy somer lsa 54 xl85 11 kv 2200 2750 144 2160 2700 142 2160 2700 142 (medium volt. leroy somer) * cos phi = 0,8 // cooling system jacket water pump thermostat(s) water charge air cooling ? mechanical radiator ? electrical driven front-end cooler ? jacket water heater
4 // / / mtu 20v4000 ds3200 / 50 hz / 380v - 11kv // control panel pre-wired control cabinet for easy application of customized controller (v1+) ? island operation (v2) ? automatic mains failure operation with ats (v3a) ? automatic mains failure operation incl. control of generator and mains breaker (v3b) ? island parallel operation of multiple gensets (v4) ? automatic mains failure operation with short (< 10s) mains parallel overlap synchronization (v5) ? mains parallel operation of a single genset (v6) ? mains parallel operation of multiple gensets (v7) ? basler controller ? deif controller complete system metering digital metering engine parameters generator protection functions engine protection sae j1939 engine ecu communications parametrization software multilingual capability multiple programmable contact inputs multiple contact outputs event recording ip 54 front panel rating with integrated gasket ? different expansion modules ? remote annunciator ? daytank control ? generator winding temperature monitoring ? generator bearing temperature monitoring ? differential protection with multi-finction protection relay ? modbus rtu-tcp gateway // circuit breaker/power distribution ? 3-pole circuit breaker ? 4-pole circuit breaker ? manual-actuated circuit breaker ? electrical-actuated circuit breaker ? stand-alone solution in seperate switch box // fuel system flexible fuel connectors mounted to base frame ? fuel filter with water separator ? switchable fuel filter with water separator ? seperate fuel cooler ? fuel cooler integrated into cooling equipment represents standard features ? represents optional features standard and optional features, continuation // starting/charging system 24v starter ? starter batteries ? battery rack & cables ? battery charger
5 // / / mtu 20v4000 ds3200 / 50 hz / 380v - 11kv represents standard features ? represents optional features standard and optional features, continuation // exhaust system ? exhaust bellows with connection flange ? exhaust silencer with 10 db(a) sound attenuation ? exhaust silencer with 30 db(a) sound attenuation ? exhaust silencer with 40 db(a) sound attenuation ? y-connection-pipe // mounting system welded base frame resilient engine and generator mounting modular base frame design
6 // / / mtu 20v4000 ds3200 / 50 hz / 380v - 11kv subject to change. | 3238691 | edition 01/14 | enc 2014-07. mtu onsite energy a rolls-royce power systems brand www.mtuonsiteenergy.com weights and dimensions sound data // consult your local mtu onsite energy distributor for sound data. emissions data // consult your local mtu onsite energy distributor for emissions data. rating definitions and conditions // data center continuous power ratings apply to data center installations where a reliable utility power is available and comply with uptime institute tier iii and iv requirements. at constant or varying load, the number of generator set operating hours is unlimited. a 10% overload capacity is available for one hour in twelve. ratings are in accordance with iso 8528-1, iso 3046-1, bs 5514 and as 2789. average load factor: 100%. // deration factor: altitude: consult your local mtu onsite energy power generation distributor for altitude derations. temperature: consult your local mtu onsite energy power generation distributor for temperature derations. rated power is available up to 40c and 100m above sea level. system dimensions (l x w x h) weight (dry/less tank) open power unit (opu) 6315 x 1810 x 2332 mm 19955 kg materials and speci? cations subject to change without notice. weights and dimensions are based on open power units and are estimates only. consult the factory for accurate weights and dimen sions for your speci? c engine-generator set. drawing above for illustration purposes only, based an standard open power 400 volt engine-generator set. lengths may vary with other voltages. do not use for installation design. see website for unit speci? c template drawings.


▲Up To Search▲   

 
Price & Availability of MTU20V4000DS3200

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X